Multiple reflections on a mismatched transmission line

Introduction

This applet visually demonstrates multiple reflections of a transmitted ramp or pulse on a transmission line in the time domain. The reflections are due to a mismatched load and/or source resistance and not an impedance. Due to the limitations of space and patience, the number of reflections that the applet shows are three from the mismatched load and three from the mismatched source. This should be sufficient to be able to imagine what would be happening to the amplitudes of the reflected pulses and the voltages on the line as more reflections occur. A document, reflections.doc, that describes the theory the reflections on a transmission line is provided if required.

Figure 1 Applet input controls

As shown in Figure 1, the inputs required by the applet are, in order of entry:

The text fields: ) give the line characteristic impedance as 50W and the velocity of propagation as 2/3 the speed of light. The source and load resistance if each is different from the characteristic impedance of the line, together produce two reflection coefficients that can be both positive, negative or one positive and the other negative. The effect of these reflection coefficients are produce an inverted or non-inverted reflected pulse or ramp voltage on the line. The voltage sum history permits the cumulative voltage at the load, at the source or on the line to be observed for the duration of the six reflections that occur on the line.
The screen text output (in blue) provides information on the derived quantities which are also characteristics of the line. From the capacitance and inductance inputs (per unit length), the characteristic impedance and velocity of the signal is derived, which in this case is 50 Ohms and 2/3 speed of light, respectively. From the source resistance input and the characteristic impedance of the line, the source reflection coefficient is derived. Similarly, from the load resistance and the characteristic impedance of the line the load reflection coefficient is found. From the velocity of the signal and the line length, the time it takes for a pulse to travel down the line is also found. This is given as the "Line Length in us". Again, from the velocity of the signal, the pulse with can be expressed in terms of length, that is the distance travelled in so many microseconds. This is shown as the "Pulse Width in metres."

Figure 2, shows a screen shot of a reflected ramp at the load and a partial voltage history of the distribution with time.

Figure 2 A reflected ramp at the load

Figure 3 shows a screen shot where all reflections have finished and the complete voltage sum history is displayed for the time duration of the original ramp entering the line to the final reflection exiting the line.
Figure 3 Voltage sum history for the distribution mode (Sitting on the front of the wave as it travels down the line)

A document, reflections.doc, that describes the theory the reflections on a transmission line is provided if required.

The source code (version Rev.1 99/12/17) is available according to the GNU Public License.


Tony Townsend, tonyart@ieee.org